|
A
|
|
Absolute Pressure
|
|
The total of the indicated gage pressure plus
the atmospheric pressure. Abbreviated "psia" for pounds per
square inch absolute.
|
|
Absolute Temperature
|
|
Temperature measured from absolute zero using
an absolute temperature scale (e.g. Kelvin).
|
|
Absolute Zero
|
|
Temperature at which all molecular motion
ceases (-460 °F, -273.15 °C, and 0 K.)
|
|
Aeration
|
|
Act of combining substance with air.
|
|
AFUE - Annual Fuel Utilization Efficiency
|
|
The ratio of annual output of useful energy or
heat to the annual energy input to the furnace.
|
|
AHU (Air Handling Unit)
|
|
The inside part of the A/C system that contains
the blower, cooling (evaporator) coil, and heater.
|
|
Air Change
|
|
The amount of air required to completely
replace the air in a room or building; not to be confused with
recirculated air
|
|
Air Coil
|
|
Coil on some types of heat pumps used either as
an evaporator or condenser.
|
|
Air Diffuser
|
|
Air distribution outlet or grille designed to
direct airflow into desired patterns.
|
|
Air Diffusion
|
|
Distribution of the air in a space, called the
treated space, by means of devices, called air terminal devices, in a
manner so as to meet certain specified conditions, such as air change
rate, pressure, cleanliness, temperature, humidity, air velocity and noise
level.
|
|
Air Distribution
|
|
The transportation of a specified air flow to
or from the treated space or spaces, generally by means of ductwork.
|
|
Air Gap
|
|
The space between magnetic poles or between
rotating and stationary assemblies in a motor or generator.
|
|
Air Handler
|
|
Fan/blower, filter and housing parts of a
system.
|
|
Air Infiltration
|
|
Leakage of air into rooms through cracks,
windows doors and other openings.
|
|
Air Sensor
|
|
A device that registers changes in air
conditions such as pressure, velocity, temperature, or moisture content.
|
|
Air Source Equipment
|
|
Heat pumps or air conditioners that uses the
outdoor air to transfer heat to and from the refrigerant in the unit.
|
|
Air Terminal Device
|
|
A device located in an opening provided at the
boundaries of the treated space to ensure a predetermined motion of air in
this space.
|
|
Air Vent
|
|
A fitting used to vent air manually or
automatically from a system.
|
|
Airflow
|
|
The volume of air moving through a blower or
duct. Units of measure are cubic feet per minute (CFM), liters per second
(LPS) or cubic meters per hour (m3h).
|
|
Anemometer
|
|
An instrument used to measure air velocities.
|
|
ARI (Air-Conditioning and Refrigeration Institute)
|
|
Air-Conditioning and Refrigeration Institute is
a nonprofit, voluntary organization comprised of heating, air conditioning
and refrigeration manufacturers. ARI publishes standards for testing and
rating heat pumps and air conditioners to provide you with a standardized
measure of comparison. So, ARI ensures a level of performance within the
industry.
|
|
ASHRAE
|
|
A leading HVAC/R Association - American Society
of Heating, Refrigerating and Air Conditioning Engineers - http://www.ashrae.org/
|
|
ASTM
|
|
American Society for Testing and Materials.
|
|
Automatic Control
|
|
Controls that react to a change in conditions
to cause the condition to stabilize.
|
|
Atmospheric Pressure
|
|
The pressure exerted upon the earth's surface
by the air because of the gravitational attraction of the earth. Standard
atmosphere pressure at sea level is 14.7 pounds per square inch (psi).
Measured with a barometer.
|
|
B
|
|
Balancing
|
|
Process of adjusting the flow of air in duct
systems, or water flow in hot-water heating systems.
|
|
Barometer
|
|
An instrument for measuring atmospheric
pressure.
|
|
Blower
|
|
An enclosed air-moving device which redirects
the airflow by 90 degrees towards one or more exit points.
|
|
BTU (British Thermal Unit)
|
|
Quantity of heat required to raise the
temperature of one pound of water one degree Fahrenheit.
|
|
Burner
|
|
A device used to prepare and burn fuel.
|
|
C
|
|
Carbon Dioxide
|
|
A by-product of natural gas combustion that is
not harmful.
|
|
Carbon Monoxide
|
|
A colorless, odorless, highly poisonous gas
produced when carbon burns without sufficient air nearby.
|
|
Centrifugal Fan
|
|
A device that draws air in axially and
discharges it radially.
|
|
CFM (Cubic Feet per Minute)
|
|
A standard measurement of airflow that
indicates how many cubic feet of air pass by a stationary point in one
minute. The higher the number, the more air is being forced through the
system.
|
|
Charge
|
|
Amount of refrigerant placed in a refrigerating
unit.
|
|
Circuit Breaker
|
|
A device that opens an electric circuit when an
overload occurs.
|
|
Combustion
|
|
A reaction called rapid oxidation or burning
produced with the right combination of a fuel, oxygen, and heat.
|
|
Comfort Zone
|
|
The range of temperatures, humidities and air
velocities at which the greatest percentage of people feel comfortable.
|
|
Condensate
|
|
The moisture collected on an evaporator coil.
|
|
Condensate Pump
|
|
A small pump used to pump condensate to a
higher level.
|
|
Condensing Temperature
|
|
The temperature at which a vapor changes to a
liquid.
|
|
Conduction
|
|
The transfer of heat through a solid material.
|
|
Conformal Coating
|
|
Material coating to protect fan from harsh
environmental conditions.
|
|
Convection
|
|
The movement of heat by fluid flow(e.g. air,
water).
|
|
COP (Coefficient Of Performance)
|
|
COP compares the heating capacity of a heat
pump to the amount of electricity required to operate the heat pump in the
heating mode.
|
|
D
|
|
Damper
|
|
A device that is located in ductwork to adjust
air flow.
|
|
DB
|
|
Dry Bulb Temperature
|
|
dB (Decibel)
|
|
A decibel describes the relative loudness of a
sound on a logarithmic scale.
|
|
Dew point
|
|
The exact temperature at which moisture begins
to form.
|
|
Direct Gas-Fired Heater
|
|
The burner fires directly in the air stream
being heated, rather than through a heat exchanger. 100% of available BTUs
are delivered to the heated space because no flue or heat exchanger is
required. This results in no wasted energy.
|
|
DOE (Department of Energy)
|
|
The Department of Energy is a federal agency in
charge of setting industry efficiency standards and monitoring the
consumption of energy sources.
|
|
Duct
|
|
A pipe or closed conduit made of sheet metal,
fiberglass board, or other suitable material used for conducting air to
and from an air handling unit.
|
|
E
|
|
EER (Energy Efficiency Ratio)
|
|
A ratio calculated by dividing the cooling
capacity in Btu's per hour (Btuh) by the power input in watts at any given
set of rating conditions, expressed in Btuh per watt (Btuh/watt). EER
& SEER can not be compared equally. Air source equipment is rated by
SEER and geothermal equipment is rated by EER. EER changes with the inside
and outside conditions, falling as the temperature difference between
inside and outside gets larger.
|
|
Efficiency
|
|
A rating on comfort equipment is similar to the
miles per gallon rating on your car.
|
|
EPA (Environmental Protection Agency)
|
|
Environmental Protection Agency - http://www.epa.gov/
|
|
Evaporation
|
|
The condition that occurs when heat is absorbed
by liquid and it changes to vapor.
|
|
Evaporator Coil
|
|
Part of a split-system air conditioner or heat
pump located indoors. The evaporator coil cools and dehumidifies the air
by converting liquid refrigerant into a gas, which absorbs the heat from
the air. The warmed refrigerant is then carried through a tube to the
outdoor unit (condenser coil).
|
|
Exfiltration
|
|
Uncontrolled air leakage out of a building.
|
|
Exhaust
|
|
The air flow leaving the treated space.
|
|
F
|
|
Fahrenheit Scale
|
|
The temperature scale that places the boiling
point of water at 212°F and the freezing point at 32°F.
|
|
Fan
|
|
A device that produces a pressure difference in
air to move it.
|
|
Fan Cycling
|
|
The use of a pressure control to turn a
condenser fan on and off to maintain a correct pressure within the system.
|
|
Fan Laws
|
|
A family of mathematical relationships that
allows the calculation of new operating characteristics from known system
conditions.
|
|
Filter
|
|
A device for removing dust particles from air
or unwanted elements from liquids.
|
|
Flow Coefficient
|
|
A dimensionless parameter relation air velocity
to fan tip velocity. It's used to determine approximate fan width for
centrifugal impellers.
|
|
G
|
|
Gage
|
|
An instrument for measuring pressure.
|
|
Geothermal Equipment
|
|
Heat pumps that uses the ground to transfer
heat to and from the refrigerant in the unit. The unit circulates water
through a heat exchanger in the to a closed loop buried in the ground or
by pumping water from a well through the unit.
|
|
H
|
|
Heat Exchanger
|
|
This is a device that enables furnaces to
transfer heat from combustion safely into breathable air. The primary heat
exchanger transfers heat from combustion gases to the air blowing through
the ductwork.
|
|
Heat Gain
|
|
The amount of heat gained, measured in BTU's,
from a space to be conditioned, at the local summer outdoor design
temperature and a specified indoor design condition.
|
|
Heat Loss
|
|
The amount of heat lost, measured in BTU's from
a space to be conditioned, at the local winter outdoor design temperature
and a specified indoor design condition.
|
|
Heat Pump
|
|
Compression cycle system used to supply heat to
a temperature controlled space. Same system can also remove heat from the
same space.
|
|
Humidifier
|
|
A device that adds moisture to warm air being
circulated or directed into a space.
|
|
Humidity Sensor
|
|
A device designed to regulate humidity input by
reacting to changes in the moisture content of the air.
|
|
Humidity
|
|
The amount of moisture in the air. Air
conditioners remove moisture for added comfort.
|
|
HVAC
|
|
Heating, Ventilating and Air Conditioning
|
|
I
|
|
Inches of Water Gage or Column (IN WG or IN WC)
|
|
A unit of air pressure measurement equal to the
pressure exerted by a column of water 1 inch high.
|
|
IAQ
|
|
Indoor Air Quality
|
|
IGBT
|
|
Insulated Gate Bipolar Transistor.
|
|
Impedance
|
|
The resistance or opposition to airflow in a
system. Same as back pressure or static pressure.
|
|
Impeller
|
|
The component of a fan assembly that is
composed of a number of contoured blades.
|
|
Induction
|
|
Process by which the primary air sets into
motion an air volume, called secondary air, in the room.
|
|
K
|
|
KW
|
|
Kilowatt, equals 1000 Watts.
|
|
KWh
|
|
Kilowatt hour is the amount of kilowatts of
electricity used in one hour of operation of any equipment.
|
|
L
|
|
Latent Heat
|
|
Heat, that when added or removed, causes a
change in state - but no change in temperature.
|
|
Linear Feet per Minute (LFM)
|
|
A unit of measurement. The velocity of the air.
|
|
M/N/O
|
|
Manometer
|
|
An instrument that measures air pressure
differences between locations. Tubes are usually attached to a manometer
and run to the spaces where pressures are measured. Essentially a U-tube
partly filled with a liquid, usually water, mercury or a light oil. The
pressure exerted on the liquid is indicated by the liquid displaced. A
manometer can be used as a differential pressure gage.
|
|
Motor
|
|
A device that converts electrical energy into
mechanical energy. A motor can operate on direct current (DC) or
alternating current (AC) voltage supply, not both.
|
|
P/Q
|
|
PCB
|
|
Printed Circuit Board.
|
|
Pascals (Pa)
|
|
A small unit of air pressure.
|
|
Pitot Tube
|
|
A sensing device used to measure total
pressures in a fluid stream. It was invented by a French physicist, Henri
Pitot, in the 1700's.
|
|
Plenum
|
|
An air flow passage.
|
|
Pressure Coefficient
|
|
A dimensionless parameter relating the static
pressure potential of a fan to its tip velocity pressure equivalent. It's
used to determine approximate fan diameter.
|
|
R
|
|
Radiation
|
|
The transfer of heat directly from one surface
to another. (No intermediate air acting as a transfer mechanism required).
|
|
RH
|
|
Relative Humidity
|
|
RPM
|
|
Revolutions per minute, the measurement of fan
blade speed.
|
|
Rotor
|
|
The rotating part of the motor which includes
the propeller assembly.
|
|
S
|
|
Saturation Temperature
|
|
Also referred to as the boiling point or the
condensing temperature. This is the temperature at which a refrigerant
will change state from a liquid to a vapor or visa versa.
|
|
SEER (Seasonal Energy Efficiency Ratio)
|
|
The total cooling of a central unitary air
conditioner or unitary heat pump in BTU's during its normal annual usage
period for cooling divided by the total electric energy input in
watt-hours during the same period.
|
|
Sensible Cooling Load
|
|
The heat gain of the home due to conduction,
solar radiation, infiltration, appliances, people, and pets. Burning a
light bulb, for example, adds only sensible load to the house. This
sensible load raises the dry-bulb temperature.
|
|
Sensible Heat
|
|
Heat, that when added or removed, causes a
change in temperature but not in state.
|
|
Sound Attenuators
|
|
Components which are inserted into the air
distribution system and designed to reduce airborne noise which is
propagated along the ducts.
|
|
Specific Speed
|
|
A dimensionless parameter based on fan
rotational speed, flow rating and pressure rating. It's a tool used to
select the type of fan for a specific application. Each Different fan type
achieves peak efficiency at a unique specific speed range.
|
|
Standard Cubic Feet Per Minute (SCFM)
|
|
The volumetric rate of airflow at standard air
conditions.
|
|
Static Efficiency
|
|
A measure of an air mover's efficiency based on
its air horsepower in terms of flow and static pressure vs. required shaft
input power.
|
|
Static Pressure
|
|
The difference in air pressure between the
suction side and pressure side of the blower. Unit of measure is inches of
water column (in. wc) or Pascals (Pa).
|
|
Stator
|
|
The part of the motor that is fixed, typically
found in the hub of the fan.
|
|
System Impedance
|
|
The resistance to air flow when moving air
through an airflow system. Examples: air filters, air grilles and abrupt
changes in flow direction.
|
|
System Operating Point
|
|
The point of operation of the air mover on its
air performance curve. It is described by an airflow and static pressure
point. The operating point is that point on the air mover performance
curve where the system resistance curve crosses the air performance curve.
|
|
T
|
|
Thermometer
|
|
An instrument used to detect differences in the
level of heat.
|
|
Thermostat
|
|
A device that senses temperature change and
changes some dimension or condition within to control an operating device.
|
|
Ton
|
|
A unit of measure for cooling capacity. One ton
= 12,000 BTUs per hour.
|
|
Total Efficiency
|
|
A measure of an air movers efficiency based on
its air horsepower in terms of flow and total pressure vs. required shaft
input power.
|
|
U
- Z
|
|
Ventilator
|
|
Captures heating or cooling energy from stale
indoor air and transfers it to fresh incoming air.
|
|
Venturi
|
|
The housing or frame of the fan.
|
|
W
|
|
Watt, the SI unit of power. In electricity it
is Volts x Amps.
|
|
WB
|
|
Wet Bulb
|
|
WC (Water Column)
|
|
Common measure of air pressure used in HVAC
systems.
|